Back to the backflow review queue

Backflow assembly test: 2220 Mill Creek Rd

Filed Nov 26, 2026 by Logan Benton, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Nov 26, 2026
Assembly type
RP
Serial number
B634163
Size
1
Test gauge serial
G-7340
Gauge calibration date
Oct 22, 2026
Check valve 1
8.2 psid
Check valve 1 closed tight
Yes
Check valve 2
1.4 psid
Relief valve opened at
4.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Benton, current on the service date
  • All required fields present
  • Address matches parcel 013-69-01198
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Property

2220 Mill Creek Rd
Owner: Drew Vance
Parcel 013-69-01198