Back to the backflow review queue

Backflow assembly test: 3520 Stone Gate Rd

Approved

Filed Jan 6, 2026 by Sam Brandt, Patriot Backflow Testing. Filed from a phone.

Report

Date of service
Jan 6, 2026
Assembly type
PVB
Serial number
K153424
Size
1
Test gauge serial
G-9978
Gauge calibration date
May 17, 2025
Check valve 1
6.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Sam Brandt, current on the service date
  • All required fields present
  • Address matches parcel 019-22-01082
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

3520 Stone Gate Rd
Owner: Quinn Marsh
Parcel 019-22-01082