Backflow assembly test: Crossroads Pizza

Approved

Filed Dec 9, 2025 by Sam Brandt, Patriot Backflow Testing. Filed from a phone.

Report

Date of service
Dec 9, 2025
Assembly type
RP
Serial number
W705458
Size
1 1/2
Test gauge serial
G-4323
Gauge calibration date
Sep 18, 2025
Check valve 1
8.5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.7 psid
Relief valve opened at
1.7 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Sam Brandt, current on the service date
  • All required fields present
  • Address matches parcel 019-46-01342
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.