Backflow assembly test: 4913 Mill Creek Ct

Approved

Filed Feb 14, 2025 by Taylor Wexler, Lakeside Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Feb 14, 2025
Assembly type
RP
Serial number
Z450206
Size
3/4
Test gauge serial
G-1840
Gauge calibration date
Apr 29, 2024
Check valve 1
5.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.3 psid
Relief valve opened at
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Taylor Wexler, current on the service date
  • All required fields present
  • Address matches parcel 019-76-01225
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.