Back to the backflow review queue

Backflow assembly test: 8981 Hickory Ct

Approved

Filed Aug 3, 2026 by Morgan Calloway, Lakeside Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Aug 3, 2026
Assembly type
RP
Serial number
Z936830
Size
1
Test gauge serial
G-2375
Gauge calibration date
Jun 13, 2026
Check valve 1
8.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3 psid
Relief valve opened at
3.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Calloway, current on the service date
  • All required fields present
  • Address matches parcel 019-67-01209
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8981 Hickory Ct
Owner: Reese Ramirez
Parcel 019-67-01209