Backflow assembly test: 6992 Old Church Way

Approved

Filed Sep 20, 2025 by Sam Brandt, Patriot Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Sep 20, 2025
Assembly type
RP
Serial number
A978390
Size
1
Test gauge serial
G-9232
Gauge calibration date
Jan 5, 2025
Check valve 1
4.9 psid
Check valve 1 closed tight
Yes
Check valve 2
2.9 psid
Relief valve opened at
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Sam Brandt, current on the service date
  • All required fields present
  • Address matches parcel 019-17-01181
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

6992 Old Church Way
Owner: Hayden Harlow
Parcel 019-17-01181