Back to the backflow review queue

Backflow assembly test: Corner Apartments

Approved

Filed Mar 28, 2025 by Morgan Calloway, Lakeside Plumbing & Backflow. Filed from a phone.

Report

Date of service
Mar 28, 2025
Assembly type
DC
Serial number
K810358
Size
4
Test gauge serial
G-2131
Gauge calibration date
Feb 8, 2025
Check valve 1
9 psid
Check valve 1 closed tight
Yes
Check valve 2
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Calloway, current on the service date
  • All required fields present
  • Address matches parcel 019-48-01205
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

2367 Quarry Dr
Owner: Vance Holdings LLC
Parcel 019-48-01205