Backflow assembly test: Riverside Animal Hospital

Approved

Filed Aug 16, 2024 by Sam Brandt, Patriot Backflow Testing. Filed from a phone.

Report

Date of service
Aug 16, 2024
Assembly type
DC
Serial number
K947960
Size
1 1/2
Test gauge serial
G-5853
Gauge calibration date
May 27, 2023
Check valve 1
5.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Sam Brandt, current on the service date
  • All required fields present
  • Address matches parcel 019-28-01276
  • Test gauge calibration is more than a year old.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.