Back to the backflow review queue

Backflow assembly test: 3170 Old Church Trl

Approved

Filed Sep 29, 2025 by Sam Brandt, Patriot Backflow Testing. Filed from a phone.

Report

Date of service
Sep 29, 2025
Assembly type
RP
Serial number
W182819
Size
3/4
Test gauge serial
G-1471
Gauge calibration date
Dec 17, 2024
Check valve 1
7.9 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Relief valve opened at
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Sam Brandt, current on the service date
  • All required fields present
  • Address matches parcel 019-82-01007
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

3170 Old Church Trl
Owner: Logan Hollins
Parcel 019-82-01007