Back to the backflow review queue

Backflow assembly test: Riverside Dental

Approved

Filed May 30, 2026 by Morgan Calloway, Lakeside Plumbing & Backflow. Filed from a phone.

Report

Date of service
May 30, 2026
Assembly type
RP
Serial number
B945790
Size
1 1/2
Test gauge serial
G-6208
Gauge calibration date
Aug 30, 2025
Check valve 1
6.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
3.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Calloway, current on the service date
  • All required fields present
  • Address matches parcel 019-66-01246
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

5747 Hickory Ct
Owner: Ashby Holdings LLC
Parcel 019-66-01246