Backflow assembly test: Station Market

Approved

Filed Oct 9, 2026 by Riley Kessler, Patriot Backflow Testing. Filed from a phone.

Report

Date of service
Oct 9, 2026
Assembly type
RP
Serial number
K988896
Size
1
Test gauge serial
G-7544
Gauge calibration date
Jul 11, 2026
Check valve 1
5.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Relief valve opened at
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Kessler, current on the service date
  • All required fields present
  • Address matches parcel 019-54-01288
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

3421 Quarry Dr
Owner: Kessler Holdings LLC
Parcel 019-54-01288