Backflow assembly test: 2964 Fox Run Trl

Approved

Filed Sep 5, 2024 by Morgan Calloway, Lakeside Plumbing & Backflow. Filed from a phone.

Report

Date of service
Sep 5, 2024
Assembly type
RP
Serial number
W544946
Size
3/4
Test gauge serial
G-1201
Gauge calibration date
Nov 21, 2023
Check valve 1
6.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.8 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Calloway, current on the service date
  • All required fields present
  • Address matches parcel 019-82-01097
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.