Back to the backflow review queue

Backflow assembly test: Corner Car Wash

Approved

Filed Sep 9, 2024 by Morgan Calloway, Lakeside Plumbing & Backflow. Filed from a phone.

Report

Date of service
Sep 9, 2024
Assembly type
RP
Serial number
A697197
Size
1
Test gauge serial
G-4342
Gauge calibration date
Feb 27, 2024
Check valve 1
6.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Relief valve opened at
4.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Calloway, current on the service date
  • All required fields present
  • Address matches parcel 019-29-01168
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

2764 Hickory Way
Owner: Wexler Holdings LLC
Parcel 019-29-01168