Backflow assembly test: 6012 Cedar Hollow Trl

Approved

Filed Jul 4, 2025 by Avery Ramirez, Clearwater Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Jul 4, 2025
Assembly type
DC
Serial number
Z561819
Size
1
Test gauge serial
G-3815
Gauge calibration date
May 15, 2025
Check valve 1
0.5 psid
Check valve 1 closed tight
No
Check valve 2
3.2 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 021-88-01056
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

6012 Cedar Hollow Trl
Owner: Logan Benton
Parcel 021-88-01056