Backflow assembly test: 8147 Hickory Ct

Approved

Filed Jun 25, 2025 by Cameron Danner, Heritage Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jun 25, 2025
Assembly type
PVB
Serial number
A159199
Size
3/4
Test gauge serial
G-4826
Gauge calibration date
Nov 24, 2024
Check valve 1
6.5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Danner, current on the service date
  • All required fields present
  • Address matches parcel 021-69-01316
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

8147 Hickory Ct
Owner: Hayden Danner
Parcel 021-69-01316