Back to the backflow review queue

Backflow assembly test: 5221 Cedar Hollow Dr

Approved

Filed Jan 6, 2025 by Alex Ashby, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jan 6, 2025
Assembly type
RP
Serial number
A133008
Size
3/4
Test gauge serial
G-5144
Gauge calibration date
Jul 17, 2024
Check valve 1
8 psid
Check valve 1 closed tight
Yes
Check valve 2
1 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Ashby, current on the service date
  • All required fields present
  • Address matches parcel 021-90-01163
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

5221 Cedar Hollow Dr
Owner: Avery Okafor
Parcel 021-90-01163