Back to the backflow review queue

Backflow assembly test: 2036 Sycamore Ct

Approved

Filed Jun 4, 2025 by Morgan Stroud, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jun 4, 2025
Assembly type
DC
Serial number
W568617
Size
1
Test gauge serial
G-5820
Gauge calibration date
Apr 10, 2025
Check valve 1
7.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Stroud, current on the service date
  • All required fields present
  • Address matches parcel 021-32-01141
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

2036 Sycamore Ct
Owner: Taylor Ramirez
Parcel 021-32-01141