Back to the backflow review queue
Backflow assembly test: Main Street Market
ApprovedFiled Apr 11, 2025 by Parker Ramirez, Heritage Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Apr 11, 2025
- Assembly type
- DC
- Serial number
- W389303
- Size
- 1
- Test gauge serial
- G-1501
- Gauge calibration date
- Jan 9, 2025
- Check valve 1
- 0.4 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.9 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Ramirez, current on the service date
- All required fields present
- Address matches parcel 021-43-01331
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
2546 Quarry Ct
Owner: Stroud Holdings LLC
Parcel 021-43-01331