Backflow assembly test: 5229 Laurel Way

Approved

Filed Jul 22, 2026 by Avery Ramirez, Clearwater Backflow Testing. Filed from a phone.

Report

Date of service
Jul 22, 2026
Assembly type
DC
Serial number
A928328
Size
1
Test gauge serial
G-5470
Gauge calibration date
Dec 12, 2025
Check valve 1
4.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 021-95-01296
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

5229 Laurel Way
Owner: Parker Stroud
Parcel 021-95-01296