Backflow assembly test: 3410 Cedar Hollow Ln

Approved

Filed Oct 15, 2025 by Morgan Stroud, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 15, 2025
Assembly type
PVB
Serial number
B923521
Size
1
Test gauge serial
G-4520
Gauge calibration date
Jan 30, 2025
Check valve 1
3.1 psid
Check valve 1 closed tight
Yes
Check valve 2
3.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Stroud, current on the service date
  • All required fields present
  • Address matches parcel 021-95-01093
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.