Backflow assembly test: 7934 Fox Run Dr

Approved

Filed Oct 7, 2025 by Riley Pruitt, Heritage Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 7, 2025
Assembly type
RP
Serial number
A468317
Size
1
Test gauge serial
G-7199
Gauge calibration date
Feb 12, 2025
Check valve 1
3.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 021-89-01200
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

7934 Fox Run Dr
Owner: Casey Ramirez
Parcel 021-89-01200