Back to the backflow review queue

Backflow assembly test: 2929 Hickory Rd

Approved

Filed Jul 3, 2026 by Parker Ramirez, Heritage Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jul 3, 2026
Assembly type
RP
Serial number
A786161
Size
1
Test gauge serial
G-4427
Gauge calibration date
Sep 19, 2025
Check valve 1
8.3 psid
Check valve 1 closed tight
Yes
Check valve 2
2.5 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 021-20-01081
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

2929 Hickory Rd
Owner: Hayden Benton
Parcel 021-20-01081