Back to the backflow review queue

Backflow assembly test: 412 Meadow Lark Ct

Approved

Filed Dec 4, 2025 by Morgan Stroud, Patriot Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Dec 4, 2025
Assembly type
DC
Serial number
W468471
Size
1
Test gauge serial
G-2441
Gauge calibration date
Feb 21, 2025
Check valve 1
9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Stroud, current on the service date
  • All required fields present
  • Address matches parcel 021-34-01009
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

412 Meadow Lark Ct
Owner: Reese Hollins
Parcel 021-34-01009