Back to the backflow review queue

Backflow assembly test: Station Taqueria

Approved

Filed Jul 3, 2026 by Jordan Vance, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Jul 3, 2026
Assembly type
RP
Serial number
B818395
Size
4
Test gauge serial
G-5539
Gauge calibration date
Sep 21, 2025
Check valve 1
3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jordan Vance, current on the service date
  • All required fields present
  • Address matches parcel 025-74-01002
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

4965 Hickory Ct
Owner: Ashby Holdings LLC
Parcel 025-74-01002