Back to the backflow review queue

Backflow assembly test: 8946 Quarry Way

Approved

Filed Oct 4, 2024 by Jordan Vance, Valley Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Oct 4, 2024
Assembly type
PVB
Serial number
W954545
Size
1
Test gauge serial
G-1460
Gauge calibration date
Jul 31, 2023
Check valve 1
5.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jordan Vance, current on the service date
  • All required fields present
  • Address matches parcel 025-54-01006
  • Test gauge calibration is more than a year old.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

8946 Quarry Way
Owner: Hayden Kessler
Parcel 025-54-01006