Backflow assembly test: Golden Market
ApprovedFiled Nov 23, 2025 by Jordan Vance, Valley Backflow Testing. Filed from a phone.
Report
- Date of service
- Nov 23, 2025
- Assembly type
- RP
- Serial number
- K523199
- Size
- 4
- Test gauge serial
- G-9028
- Gauge calibration date
- Aug 7, 2025
- Check valve 1
- 5.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.3 psid
- Relief valve opened at
- 2.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Jordan Vance, current on the service date
- All required fields present
- Address matches parcel 025-64-01083
- Readings in range, no flags
- Result: passing. Next due date resets when approved.