Backflow assembly test: 1680 Ridgeview Way
ApprovedFiled Feb 27, 2025 by Jordan Vance, Valley Backflow Testing. Filed from a phone.
Report
- Date of service
- Feb 27, 2025
- Assembly type
- RP
- Serial number
- W494791
- Size
- 1
- Test gauge serial
- G-2226
- Gauge calibration date
- Mar 31, 2024
- Check valve 1
- 0.7 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.8 psid
- Relief valve opened at
- 2.7 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Jordan Vance, current on the service date
- All required fields present
- Address matches parcel 025-85-01019
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
1680 Ridgeview Way
Owner: Taylor Marsh
Parcel 025-85-01019