Backflow assembly test: Corner Brewing Co

Filed Nov 22, 2026 by Jordan Vance, Valley Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Nov 22, 2026
Assembly type
RP
Serial number
Z311947
Size
1
Test gauge serial
G-2127
Gauge calibration date
May 22, 2026
Check valve 1
7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.7 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jordan Vance, current on the service date
  • All required fields present
  • Address matches parcel 025-84-01171
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Property

4273 Turkey Hill Rd
Owner: Nguyen Holdings LLC
Parcel 025-84-01171