Back to the backflow review queue

Backflow assembly test: 5680 Laurel Ln

Approved

Filed Jul 17, 2025 by Avery Harlow, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Jul 17, 2025
Assembly type
DC
Serial number
W551305
Size
3/4
Test gauge serial
G-2721
Gauge calibration date
Feb 12, 2025
Check valve 1
6.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Harlow, current on the service date
  • All required fields present
  • Address matches parcel 025-50-01023
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

5680 Laurel Ln
Owner: Shawn Harlow
Parcel 025-50-01023