Back to the backflow review queue

Backflow assembly test: 6396 Turkey Hill Ln

Approved

Filed Sep 22, 2026 by Cameron Danner, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Sep 22, 2026
Assembly type
RP
Serial number
A450711
Size
3/4
Test gauge serial
G-1403
Gauge calibration date
Apr 11, 2026
Check valve 1
6.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3 psid
Relief valve opened at
1.4 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Danner, current on the service date
  • All required fields present
  • Address matches parcel 025-90-01299
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

6396 Turkey Hill Ln
Owner: Reese Benton
Parcel 025-90-01299