Backflow assembly test: 3066 Fox Run Ln
ApprovedFiled Sep 7, 2024 by Jordan Vance, Valley Backflow Testing. Filed from a phone.
Report
- Date of service
- Sep 7, 2024
- Assembly type
- RP
- Serial number
- W231049
- Size
- 3/4
- Test gauge serial
- G-4077
- Gauge calibration date
- Dec 20, 2023
- Check valve 1
- 3.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.2 psid
- Relief valve opened at
- 3.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Jordan Vance, current on the service date
- All required fields present
- Address matches parcel 025-32-01170
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
3066 Fox Run Ln
Owner: Shawn Nguyen
Parcel 025-32-01170