Backflow assembly test: 3066 Fox Run Ln

Approved

Filed Sep 15, 2026 by Riley Nguyen, Clearwater Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Sep 15, 2026
Assembly type
RP
Serial number
W231049
Size
3/4
Test gauge serial
G-5296
Gauge calibration date
Apr 2, 2026
Check valve 1
6.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Relief valve opened at
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 025-32-01170
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.