Back to the backflow review queue
Backflow assembly test: 3892 Old Church Trl
ApprovedFiled Jun 27, 2026 by Avery Lindqvist, Lakeside Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Jun 27, 2026
- Assembly type
- RP
- Serial number
- B980660
- Size
- 3/4
- Test gauge serial
- G-7087
- Gauge calibration date
- Apr 23, 2026
- Check valve 1
- 7.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.3 psid
- Relief valve opened at
- 2.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Avery Lindqvist, current on the service date
- All required fields present
- Address matches parcel 027-72-01203
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
3892 Old Church Trl
Owner: Taylor Vance
Parcel 027-72-01203