Back to the backflow review queue

Backflow assembly test: Golden Medical Offices

Approved

Filed Jun 23, 2026 by Logan Whitcomb, Evergreen Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jun 23, 2026
Assembly type
RP
Serial number
W191830
Size
4
Test gauge serial
G-8666
Gauge calibration date
Dec 24, 2025
Check valve 1
6.9 psid
Check valve 1 closed tight
Yes
Check valve 2
2.3 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 027-79-01332
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

7791 Fox Run Trl
Owner: Stroud Holdings LLC
Parcel 027-79-01332