Backflow assembly test: 7593 Orchard Dr

Approved

Filed Aug 17, 2025 by Avery Lindqvist, Lakeside Plumbing & Backflow. Filed from a phone.

Report

Date of service
Aug 17, 2025
Assembly type
DC
Serial number
A916753
Size
3/4
Test gauge serial
G-5248
Gauge calibration date
Jun 5, 2025
Check valve 1
5.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Lindqvist, current on the service date
  • All required fields present
  • Address matches parcel 027-34-01037
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

7593 Orchard Dr
Owner: Sam Kessler
Parcel 027-34-01037