Back to the backflow review queue

Backflow assembly test: Two Rivers Market

Approved

Filed Jul 19, 2024 by Quinn Wexler, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
Jul 19, 2024
Assembly type
DC
Serial number
A928033
Size
1
Test gauge serial
G-7862
Gauge calibration date
Feb 24, 2024
Check valve 1
7.6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Wexler, current on the service date
  • All required fields present
  • Address matches parcel 027-81-01143
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

8620 Old Church Ct
Owner: Kessler Holdings LLC
Parcel 027-81-01143