Backflow assembly test: 1183 Ridgeview Way

Approved

Filed Oct 15, 2023 by Cameron Danner, Lakeside Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 15, 2023
Assembly type
DC
Serial number
A999692
Size
3/4
Test gauge serial
G-5243
Gauge calibration date
May 25, 2023
Check valve 1
0.1 psid
Check valve 1 closed tight
No
Check valve 2
2.5 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Danner, current on the service date
  • All required fields present
  • Address matches parcel 027-89-01158
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

1183 Ridgeview Way
Owner: Jordan Danner
Parcel 027-89-01158