Backflow assembly test: 5610 Mill Creek Ln

Approved

Filed Sep 26, 2025 by Quinn Wexler, Keystone Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Sep 26, 2025
Assembly type
RP
Serial number
A585619
Size
3/4
Test gauge serial
G-9672
Gauge calibration date
Dec 27, 2024
Check valve 1
8.9 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Wexler, current on the service date
  • All required fields present
  • Address matches parcel 027-62-01078
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

5610 Mill Creek Ln
Owner: Avery Kessler
Parcel 027-62-01078