Backflow assembly test: 7907 Pine Knoll Trl
ApprovedFiled Oct 20, 2025 by Quinn Wexler, Keystone Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Oct 20, 2025
- Assembly type
- RP
- Serial number
- W669663
- Size
- 1
- Test gauge serial
- G-8718
- Gauge calibration date
- Aug 24, 2025
- Check valve 1
- 3.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.3 psid
- Relief valve opened at
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Quinn Wexler, current on the service date
- All required fields present
- Address matches parcel 027-35-01245
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
7907 Pine Knoll Trl
Owner: Rowan Stroud
Parcel 027-35-01245