Back to the backflow review queue

Backflow assembly test: 7907 Pine Knoll Trl

Approved

Filed Nov 1, 2026 by Logan Whitcomb, Evergreen Plumbing & Backflow. Filed from a phone.

Report

Date of service
Nov 1, 2026
Assembly type
RP
Serial number
W669663
Size
1
Test gauge serial
G-5682
Gauge calibration date
Feb 7, 2026
Check valve 1
8.2 psid
Check valve 1 closed tight
Yes
Check valve 2
1.6 psid
Relief valve opened at
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 027-35-01245
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

7907 Pine Knoll Trl
Owner: Rowan Stroud
Parcel 027-35-01245