Backflow assembly test: 2817 Orchard Way
ApprovedFiled Dec 30, 2025 by Avery Okafor, Lakeside Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Dec 30, 2025
- Assembly type
- RP
- Serial number
- B891763
- Size
- 3/4
- Test gauge serial
- G-7932
- Gauge calibration date
- May 27, 2025
- Check valve 1
- 8.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.6 psid
- Relief valve opened at
- 3.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Avery Okafor, current on the service date
- All required fields present
- Address matches parcel 027-86-01202
- Readings in range, no flags
- Result: passing. Next due date resets when approved.