Backflow assembly test: 361 Hickory Dr
ApprovedFiled Aug 10, 2025 by Logan Whitcomb, Evergreen Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Aug 10, 2025
- Assembly type
- DC
- Serial number
- K476289
- Size
- 3/4
- Test gauge serial
- G-8032
- Gauge calibration date
- Sep 11, 2024
- Check valve 1
- 0.5 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.2 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Logan Whitcomb, current on the service date
- All required fields present
- Address matches parcel 027-32-01229
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.