Back to the backflow review queue

Backflow assembly test: 7955 Quarry Rd

Approved

Filed Jun 9, 2025 by Logan Whitcomb, Evergreen Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jun 9, 2025
Assembly type
RP
Serial number
B925472
Size
3/4
Test gauge serial
G-1775
Gauge calibration date
Nov 20, 2024
Check valve 1
5.5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Relief valve opened at
3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 027-59-01054
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

7955 Quarry Rd
Owner: Shawn Ashby
Parcel 027-59-01054