Backflow assembly test: 1424 Orchard Way

Approved

Filed Apr 11, 2026 by Jordan Pruitt, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
Apr 11, 2026
Assembly type
PVB
Serial number
W316398
Size
1
Test gauge serial
G-8840
Gauge calibration date
Oct 22, 2025
Check valve 1
6.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jordan Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 027-54-01348
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

1424 Orchard Way
Owner: Quinn Fairley
Parcel 027-54-01348