Backflow assembly test: 9152 Orchard Ln

Approved

Filed May 1, 2025 by Jordan Pruitt, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
May 1, 2025
Assembly type
RP
Serial number
K996697
Size
1
Test gauge serial
G-3161
Gauge calibration date
Nov 18, 2024
Check valve 1
5.4 psid
Check valve 1 closed tight
Yes
Check valve 2
3.2 psid
Relief valve opened at
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jordan Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 027-91-01243
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.