Backflow assembly test: Hilltop Medical Offices

Approved

Filed Sep 27, 2023 by Avery Lindqvist, Lakeside Plumbing & Backflow. Filed from a phone.

Report

Date of service
Sep 27, 2023
Assembly type
RP
Serial number
A871316
Size
1
Test gauge serial
G-5415
Gauge calibration date
Apr 26, 2023
Check valve 1
4.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Relief valve opened at
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Lindqvist, current on the service date
  • All required fields present
  • Address matches parcel 027-66-01351
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.