Backflow assembly test: Hilltop Medical Offices
ApprovedFiled Oct 13, 2024 by Quinn Wexler, Keystone Backflow Testing. Filed from a phone.
Report
- Date of service
- Oct 13, 2024
- Assembly type
- RP
- Serial number
- A871316
- Size
- 1
- Test gauge serial
- G-2262
- Gauge calibration date
- Aug 1, 2024
- Check valve 1
- 5.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.1 psid
- Relief valve opened at
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Quinn Wexler, current on the service date
- All required fields present
- Address matches parcel 027-66-01351
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
1368 Cedar Hollow Rd
Owner: Vance Holdings LLC
Parcel 027-66-01351