Backflow assembly test: 8076 Stone Gate Trl
ApprovedFiled Jan 6, 2026 by Sam Fairley, Northstar Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Jan 6, 2026
- Assembly type
- PVB
- Serial number
- K995017
- Size
- 3/4
- Test gauge serial
- G-9280
- Gauge calibration date
- Sep 24, 2024
- Check valve 1
- 6.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.9 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Sam Fairley, current on the service date
- All required fields present
- Address matches parcel 007-90-01269
- Test gauge calibration is more than a year old.
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
8076 Stone Gate Trl
Owner: Emerson Hollins
Parcel 007-90-01269