ApprovedFiled Jan 15, 2025 by Sam Fairley, Northstar Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Jan 15, 2025
- Assembly type
- RP
- Serial number
- K297963
- Size
- 1 1/2
- Test gauge serial
- G-6480
- Gauge calibration date
- Sep 5, 2024
- Check valve 1
- 4.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.7 psid
- Relief valve opened at
- 2.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Sam Fairley, current on the service date
- All required fields present
- Address matches parcel 007-20-01126
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
2603 Ridgeview Ln
Owner: Stroud Holdings LLC
Parcel 007-20-01126