Back to the backflow review queue

Backflow assembly test: 8304 Hickory Ct

Approved

Filed Oct 15, 2025 by Parker Danner, Valley Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Oct 15, 2025
Assembly type
DC
Serial number
Z804358
Size
3/4
Test gauge serial
G-1226
Gauge calibration date
Jan 24, 2025
Check valve 1
4.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Danner, current on the service date
  • All required fields present
  • Address matches parcel 007-40-01257
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8304 Hickory Ct
Owner: Drew Ellery
Parcel 007-40-01257